HEATSTAT T2 (TMV2) Technical Information

Heatstat Home

Specification

Sales Literature
Availability

 

Optimum Operating Conditions :

Temperature setting at factory 46°C
Temperature adjustment range 35-50°C
Hot supply temperature range 55-85°C
Cold Supply temperature range
0-25°C
Minimum differential between hot and mixed water supply 5°C
Maximum static pressure
10 bar
Dynamic inlet pressure range* 0.2 - 5 bar
Maximum Flow Rate

50 l / min

* Supply pressures do not need to be equal.

Materials of Construction
Body: DZR Brass (BS EN 12164 CW 602N)
Slide Valve: Engineering Acetal
Springs: Stainless steel
Seal Components: Nitrile, EPDM

All materials are WRAS approved

 

 

Horne Engineering Ltd, PO Box 7, Rankine Street, Johnstone, SCOTLAND, PA5 8BD
Tel: +44 (0) 1505 321455 Fax: +44 (0)1505 336287 Email: sales@horne.co.uk